MX250 Microprocessor Controller in Mesa, AZ, USA
Used
Doubleclick to zoom in
Contact the seller for
additional photos and information.
Specifications
- Condition
- used
- Rating range
- Switch Dependent
- Transfer type
- Application Dependent
- Switch type
- Application Dependent
- Undervoltage dropout for source 1 and source 2
- 75-98% of nominal
- Undervoltage restore for source 1 and source 2
- 85-100% of nominal
- Underfrequency dropout for source 1 and source 2
- 90-100% of nominal
- Delay for engine cool down (u)
- 0-60 minutes
- Delay transfer to nonpreferred source (w)
- 0-5 minutes
- Delay neutraltransition time delays (dt,dw)
- 0-10 minutes
- Storage temperature
- (-30˚C - 75˚C ), -22˚F - 167˚F
- Operating temperature ambient
- 40 - 400 amp molded shell (-20˚C to 65˚C) , -4˚F to 149˚F 40 - 4000 amp all others (-20˚C to 60˚C), -4˚F to 149˚F
- Subcategory
- Ats mx contactor
- Listing ID
- 82879678
Description
ESD immunity test per EN61000-4-2 Class B(Level 4)
Electrical fast transient/burst immunity test perEN61000-4-4
Conducted and Radiated Emissions per EN55022Class B (CISPR11) (Exceeds EN55011 & MILSTD461 Class 3)
Voltage dips and interruption immunity EN61000-4-11
Conducted immunity test per EN61000-4-6(ENV50141)
Ringing wave immunity per IEEE 472(ANSIC37.90A)
Surge immunity test per EN61000-4-5 IEEE C62.41
UL, CSA and IEC listed
Radiated RF, electromagnetic field immunitytest per EN61000-4-3 (ENV50140) 10v/m
Weather and tamper resistant touchpad
Through-the-door programming and display
Multipurpose display: LEDs for continuous monitoring of switch position and source availability; a four line by twenty character LCD display for settings, functions, programming and annunciation
Simplified keypad entry – menu-driven system is designed for ease of use
Built-in diagnosis with displays for ease of troubleshooting
User settings are unaffected by power outages